How do I set bits in the output "Command Word" for the HI 1756WS?

Last updated 03-20-2014 03:05 a.m.

Question

How do I set bits in the output "Command Word" for the HI 1756WS, since this is a real value?

Answer

The easiest way to set the bits in the output "Command Word" for the HI 1756WS is to set up a separate "DINT" tag. Change the bits in this "DINT" tag and then do a COPY (COP) command into the output "Command Word".

This is also the way you would read the bits of the Statusword. Since it is in "real" format, you would do a copy command from the input table to a "DINT" tag and monitor the individual bits in this tag.